ThermOmegaTech Distributor - Washdown and Tepid Water Systems

ThermOmegaTech Temperature Control Products
ThermOmegaTech is an engineering company, established in 1983, specializes in designing and manufacturing of self-actuating thermostatic temperature control products for commercial plumbing, aerospace & defense, and industrial applications.
The ThermOmegaTech STVM® Steam and Water Washdown Station is designed for high temperature washdown to maximize efficiency and minimize downtime in food and beverage processing and other industrial facilities.
Key Features of the ThermOmegaTech STVM Washdown Station:
- Interlocking ball valves prevent steam only operation
- Automatic steam shut-off when cold water flow is interrupted
- Thermally activated over temperature shut-off
- Unique Venturi mixing design minimizes water hammer effect
- In-line serviceable mixing valve with easy to replace/clean cartridge
Other Benefits:
- Available in Brass and Stainless Steel
- Interchangeable cartridges converts easily between 185°F and 150°F
- Easy maintenance, limited down time
- Designed to fit in place of competitors hose stations
The HCX (Hot/Cold Water Mixing) Stations combine simplicity and cost effectiveness with the reliability and safety inherent in all ThermOmegaTech® washdown stations. The HCX station uses individual globe valves to mix hot and cold water to the desired proportion with the outlet temperature clearly displayed on the integrated, easy to read temperature gauge.
Key Features:
- No steam required
- Available in stainless steel or brass/bronze construction
- Simple to use and install
- Cost effective
- SmartFlow feature available for additional safety
Available Accessories:
- Hose Assemblies
- Black & White Creamery
- 25’, 50’, & 75’ lengths
- Blue Spray Nozzle
- Brass & Stainless fittings available
DTV valves are available with ½”, ¾”, and 1” NPT water connections.The DTV can be used in applications where a high temperature discharge flow to a drain/sewer must be tempered with cold water. Examples include:
- Humidifier discharge to sewer/drain
- Commercial dishwashers/warewashers
- Boiler blowdown drain lines
- Autoclave discharge
- Any excessively hot effluent flow to sewer/drain
DVT Design Features:
- Exclusive self-actuating Thermoloid® blend paraffin wax actuator
- Rugged, clog-resistant valve design
- Install using standard pipe fittings and tools
- Operates in any orientation
- Modulates to conserve cooling water
- Effluent tempering capacity limited only by cold water flow rate through DTV
DVT Benefits:
- Self-operating – no external power source required
- Compliant with drain temperature limitations of plumbing codes
- Prevents damage to PVC piping due to over-temperature conditions
- Minimizes water waste
- Easy to install
- Adaptable to almost any drain size
Freeze Protection
HAT/FP & IC/FP Valves
Benefits:
- Protects against freeze damage
- Self-actuating - requires no external power
- Primary protection or fail-safe backup
- Fast Response
- Discharges minimum amount of water required
HAT/FP:
- Available in ½” & ¾”
- Applications: Safety Showers, Fire Lines, Condensate Systems, Pumps, Backup protection on traced systems
- Available in 303SS body with Brass or 303SS actuator or All 316SS Body and Actuator
- Opens at 35°F and is fully closed at 40°F (other temps are available but with a 10°F curve)
- Ability to sense ambient OR fluid temperature (RF=Reverse Flow)
- Can withstand pressures up to 300 PSIG (ambient sensing) and 150 PSIG (fluid sensing)
IC/FP:
- Available in ½” & ¾”
- Applications: Protection of Piping, Safety Showers, Spray Nozzles or Backup protection for traced systems
- Available in all 303SS, 316SS and Brass
- Opens at 35°F and is fully closed at 40°F
- Only fluid sensing
- Can withstand pressures up to 150 PSIG (1/2”) and 100 PSIG (3/4”)
Scald Protection
HAT/SP & IC/SP Valves
Benefits:
- HAT/SP temperatures up to 105F meet ANSI Z358.1 standards
- Protects safety showers from over-temperature
- conditions, keeping personnel safe
- Self-operating, no power or signal required
- Two wrench flats for easy installation
- Discharges the minimum amount of water required
HAT/SP:
- Available in ½” & ¾”
- Applications: Safety Showers, outdoor sinks, anywhere scalding can occur
- Available in 303SS body with Brass or 303SS actuator or All 316SS Body and Actuator
- Opens at 105°F and is fully closed at 95°F (other temp options available)
- Ability to sense ambient OR fluid temperature (RF=Reverse Flow)
- Can withstand pressures up to 300 PSIG (ambient) and 150 PSIG (fluid)
IC/SP:
- Available in ½” & ¾”
- Applications: Solar radiation or overheating in traced lines at point of use
- Available in all 303SS, 316SS and Brass
- Opens at 105°F and is fully closed at 95°F (other temp options available)
- Only fluid sensing
- Can withstand pressures up to 150 PSIG (1/2”) and 100 PSIG (3/4”)
Therm-O-Mix (TOM Station) Steam Water Heater
Features:
- Instantaneous tepid water for safety shower/eyewash stations
- No electricity is needed
- Plant steam and water do not mix
- Redundant safety controls for over-temperature protection
- Standard pressure unit available for 45-60 PSIG steam pressure
- Low pressure unit available for 15-30 PSIG steam pressure
- Durable enclosure can be readily removed for service
- Small install footprint – 19 7/8” x 14 ¼” x 26”
- Meets ANSI Z358.1 Standards
- Mixing valve designed to meet ASSE 1071 standards
Emergency Safety Shower (ESS) Electric Water Heater
Features:- Heavy Duty Construction
- ½” thick Hydrastone cement lining provides tank longevity.
- Copper-silicon alloy tappings cannot rust or corrode.
- High impact composite jacket cannot rust or corrode and eliminates potential damage during installation and transit.
- 3" thick polyurethane foam insulation reduces standby heat loss by over 24% compared to industry standard 2" insulated tanks. Safety
- Factory packaged with the Therm-O-Mix® Station/WWM, a mixing valve designed specifically for emergency drench systems to ensure a constant flow of tepid water per ANSI Z358.1 Standards.
- Mixing valve prohibits delivery of overheated water to prevent scalding.
- Water heater provides tepid water even when an accident causes a loss of electric power.
- Reduces the risk of Legionella because water is stored at an elevated temperature.